Inrush Current
Measurement
Worst
case inrush current occurs at high line, when the customer energizes the
product at peak input line voltage.
This occurs at the 90°
and 270° points
along the input line waveform (assuming a sinusoidal input wave). The only way to test this reliably is either
to make and time the connection electronically, or to synthesize a waveform
that starts at zero and steps to the peak high line condition. The latter method affords the most
control. The amplifier used must
satisfy IEC Standard 4-11 which states that a generator used for the purpose of
inrush current testing must not be taxed to more than 75% of it’s current
rating at any time during the test.
Generators capable of 500 Amperes or more output current may be taxed to
a higher percentage of their maximum.
In any case, the output voltage loop rise time of the generator (as it
is programmed to transition from zero volts to 375 volts) must be less than 5
microseconds. The output voltage will
rise from zero to its maximum magnitude within 5 microseconds and trace out a
sinusoidal output from there. The power
supplies input current is measured and recorded during this time. Typically as digital storage oscilloscope is
used to measure the voltage drop across a current shunt. The scope is triggered from the low-level
oscillator signal driving the output waveform.
Pacific Power Source Corporation offers
a general-purpose ac power source that can be programmed with the necessary
waveform for inrush current testing and measurement. This line of power sources is called the TMX Series Power Sources. Some special
considerations must be taken into account when measuring inrush current
with these power sources.